What are the testing requirements for tamper switches in a fire suppression system, and why are they important?

According to NFPA 25 (2011), tamper switches, which monitor control valves, should be tested semiannually. During the test, the signal should activate within two handwheel revolutions or when the valve stem has moved one-fifth of the distance from its normal position. Proper testing is crucial to ensure reliable operation.

Additional Resource: NFPA 72